TechnicalContact Us

Pressure Reducing Valve (Feed Valve)
Application

Low pressure hot water systems.

Video

Pressure Reducing Valve.
Run-time: 18 seconds

Requires Windows Media Player to be installed.

Standards
  • Complies with NZ Building Code G12 (2001)
  • Complies with NZS 4608:1992
  • Patent No. 504476
Specifications

Inlet: 15mm, 1/2" BSP (male)
Outlet: 20mm 3/4" BSP (male)
Length 138mm
  • Set pressures
    • FV3.7  -  35 kPa [5 P.S.I.]
    • FV7.6  -  65 kPa [9 P.S.I.]
    • FV12.2  -  110 kPa [16 P.S.I.]
  • Adjustable pressure range
    • FV3.7 & FV7.6  -  15 to 100 kPa [2 to 14 P.S.I.]
    • FV12.2  -  25 to 150 kPa [4 to 22 P.S.I.]
  • Maximum Inlet Pressure and Temperature
    • Plastic Cap: 2000 kPa [290 P.S.I.] @ 65°C
    • Brass Cap: 2000 kPa [290 P.S.I.] @ 80°C
  • Compensated to give constant outlet pressure regardless of inlet pressure.
  • Silicon rubber diaphragm and washer.
  • DR (Dezincification Resistant) brass.
Flow Chart


Installation
  • Refer to Technical Area for installation guide.
  • Can be installed in any orientation.
  • Do NOT install in the ground.
  • Do NOT apply heat near valve during installation.
  • Valve may require adjustment on site. To increase pressure turn adjusting screw clockwise (1 ˝ turns = 1 metre head).
  • Valve must be either valve vented or open vented.
  • For increased flow rates or inlet pressure below 200 kPa [29 P.S.I.], two valves in parallel may be required.
  • Where two valves are in parallel, each must have isolating valves on inlet.
Sectional View


Product Codes

FV3.7  
FV7.6  
FV12.2  
MP7.6 Matched Pair (FV7.6 & RV7.6)
MP12.2 Matched Pair (FV12.2 & RV12.2)
4in1 3.7 4 in 1 (FV3.7 & FS15)
4in1 7.6 4 in 1 (FV7.6 & FS15)
4in1 12.2 4 in 1 (FV12.2 & FS15)
HFV3.7 Hot Water Feed Valve (Brass Cap)
HFV7.6 Hot Water Feed Valve (Brass Cap)
HFV12.2 Hot Water Feed Valve (Brass Cap)


Design by Burning Chrome© APEX Valves Limited.PrivacyWarranty