Cold Water Expansion Valve
Application

Low pressure and high (mains) pressure hot water systems.

Video

Low Pressure Cold Water Expansion Valve.
Run-time: 18 seconds

High Pressure Cold Water Expansion Valve.
Run-time: 23 seconds

Requires Windows Media Player to be installed.

Standards

  • Complies with NZ Building Code G12 (2001)
  • Complies with NZS 4608:1992
Specifications

Inlet/Outlet: 20mm, 3/4" BSP (male)
Drain: 15mm, 1/2" BSP (male)
Length: 62mm
  • Standard pressure settings
    • 75 kPa [11 P.S.I.]
    • 120 kPa [17 P.S.I.]
    • 500 kPa [72 P.S.I.]
    • 700 kPa [100 P.S.I.]
  • Pressure settings between 75 and 700 kPa [11 and 100 P.S.I.] may be factory set for special applications.
  • Maximum temperature: 99°C.
  • Failsafe against over pressure.
  • Flushing lever/handle to clear foreign matter from valve seat.
  • Drain may be used as cylinder drain when flushing lever/handle is activated.
  • Non-corrosive valve seat.
  • Silicon rubber diaphragm.
  • DR (Dezincification Resistant) brass.
Installation
  • Refer to Technical Area for installation guide.
  • May be installed in any orientation.
  • Drain must fall continuously to outlet.
  • Do NOT apply heat near valve during installation.
Thermal Expansion

Under normal conditions, a 180 litre hot water cylinder when heated from cold to 65°C will expel 3.6 litres of water due to thermal expansion. The amount of expansion will vary depending on the volume of hot water used and cylinder capacity.

Accessories

  • Non-return (mains pressure only): To prevent cross-connection of hot water to cold water supply.
  • Cap: Should second take off not be required.
Sectional View


Product Codes

Low Pressure
EVT7.6 75 kPa
EVT12.2 120 kPa
High Pressure
EVT500 500 kPa (use with 350 kPa Limiting Valve)
EVT700 700 kPa (use with 500 kPa Limiting Valve)